0.6/1kV XLPE or PVC or EPR insulated Power Cable
Application: Low voltage power cable is applied to fixed installation for rated voltage 0.6/1kv of power transmission and distribution line.
| 0.6/1KV 3+1 Cores, Copper or Aluminum Conductor, XLPE Insulated steel wire armour PVC sheath Power Cable | ||||||||||||
| Number of Cores and Nominal Area | Thickness of insulation | Approx. Overall Diameter & Weight | Max. DC Resistance at 20ºC | Current Rating (A) | ||||||||
| Phase | Earth/Neutral | Copper | Aluminium | Copper | Aluminium | Copper | Aluminium | |||||
| Nos×mm2 | mm | mm | Overall Dia. mm |
Weight kg/km | Overall Dia. mm |
Weight kg/km | Ohm/km | Ohm/km | Under Ground |
In Air |
Under Ground |
In Air |
| 3×2.5+1×1.5* | 0.7 | 0.7 | 17.2 | 600 | 17.2 | - | 7.41 | - | 38 | 30 | - | - |
| 3×4+1×2.5* | 0.7 | 0.7 | 17.4 | 649 | 17.4 | - | 4.61 | - | 50 | 49 | 24 | 17 |
| 3×6+1×4* | 0.7 | 0.7 | 18.6 | 769 | 18.6 | - | 3.08 | - | 65 | 55 | 35 | 27 |
| 3×10+1×6* | 0.7 | 0.7 | 20.3 | 989 | 20.3 | 763 | 1.83 | 3.08 | 89 | 78 | 49 | 37 |
| 3×16+1×10* | 0.7 | 0.7 | 22.5 | 1270 | 22.5 | 906 | 1.15 | 1.91 | 115 | 105 | 66 | 57 |
| 3×25+1×16 | 0.9 | 0.7 | 27.1 | 1857 | 27.1 | 1286 | 0.727 | 1.25 | 150 | 140 | 89 | 77 |
| 3×35+1×16 | 0.9 | 0.7 | 29.3 | 2234 | 29.3 | 1483 | 0.524 | 0.868 | 180 | 170 | 115 | 105 |
| 3×50+1×25 | 1.0 | 0.9 | 31.9 | 2828 | 31.9 | 1778 | 0.387 | 0.641 | 215 | 205 | 135 | 125 |
| 3×70+1×35 | 1.1 | 0.9 | 36.3 | 3928 | 36.3 | 2420 | 0.268 | 0.443 | 265 | 260 | 165 | 155 |
| 3×95+1×50 | 1.1 | 1.0 | 40.0 | 4956 | 40.0 | 2904 | 0.193 | 0.320 | 315 | 320 | 220 | 195 |
| 3×120+1×70 | 1.2 | 1.1 | 44.4 | 6408 | 44.4 | 3760 | 0.153 | 0.253 | 360 | 370 | 240 | 235 |
| 3×150+1×70 | 1.4 | 1.1 | 48.2 | 7456 | 48.2 | 4299 | 0.124 | 0.206 | 405 | 430 | 275 | 280 |
| 3×185+1×95 | 1.6 | 1.1 | 52.4 | 9081 | 52.4 | 5062 | 0.0991 | 0.164 | 460 | 490 | 310 | 320 |
| 3×240+1×120 | 1.7 | 1.2 | 57.9 | 11292 | 57.9 | 6045 | 0.0754 | 0.125 | 530 | 580 | 350 | 370 |
| 3×300+1×150 | 1.8 | 1.4 | 63.0 | 13648 | 63.0 | 7106 | 0.0601 | 0.100 | 590 | 660 | 410 | 440 |
| 3×400+1×185 | 2.0 | 1.6 | 71.0 | 18102 | 71.0 | 9457 | 0.047 | 0.0778 | 670 | 750 | 460 | 520 |
| Note:* means round conductor | ||||||||||||
| Four Cores, Copper or Aluminum Conductor, XLPE Insulated steel wire armour PVC sheath Power Cable | |||||||||||
| Nominal Cross Section mm2 | Thickness of Insulation mm | Approx. Overall Diameter & Weight | Max. DC Resistance at 20ºC | Current Rating( A) | |||||||
| Copper | Aluminium | Copper | Aluminium | Copper | Aluminium | ||||||
| Overall dia. mm | Weight kg/km | Overall dia. mm |
Weight kg/km | Ohm/km | Ohm/km | Under Ground |
In Air |
Under Ground |
In Air |
||
| 4×1.5* | 0.7 | 17.0 | 593 | - | - | 12.1 | - | 28 | 21 | - | - |
| 4×2.5* | 0.7 | 18.0 | 663 | 18.0 | 600 | 7.41 | - | 38 | 30 | 24 | 17 |
| 4×4* | 0.7 | 19.1 | 770 | 19.1 | 670 | 4.61 | - | 50 | 49 | 35 | 27 |
| 4×6* | 0.7 | 20.3 | 916 | 20.3 | 772 | 3.08 | - | 65 | 55 | 49 | 37 |
| 4×10* | 0.7 | 22.3 | 1148 | 22.3 | 895 | 1.83 | 3.08 | 89 | 78 | 66 | 57 |
| 4×16* | 0.7 | 24.5 | 1472 | 24.5 | 1070 | 1.15 | 1.91 | 115 | 105 | 89 | 77 |
| 4×25 | 0.9 | 27.5 | 1942 | 27.5 | 1317 | 0.727 | 1.25 | 150 | 140 | 115 | 105 |
| 4×35 | 0.9 | 29.5 | 2386 | 29.5 | 1521 | 0.524 | 0.868 | 180 | 170 | 135 | 125 |
| 4×50 | 1.0 | 32.9 | 3206 | 32.9 | 2036 | 0.387 | 0.641 | 215 | 205 | 165 | 155 |
| 4×70 | 1.1 | 36.7 | 4197 | 36.7 | 2502 | 0.268 | 0.443 | 265 | 260 | 220 | 195 |
| 4×95 | 1.1 | 40.5 | 5362 | 40.5 | 3016 | 0.193 | 0.320 | 315 | 320 | 240 | 235 |
| 4×120 | 1.2 | 45.3 | 6908 | 45.3 | 3940 | 0.153 | 0.253 | 360 | 370 | 275 | 280 |
| 4×150 | 1.4 | 50.0 | 8327 | 50.0 | 4683 | 0.124 | 0.206 | 405 | 430 | 310 | 320 |
| 4×185 | 1.6 | 54.2 | 10044 | 54.2 | 5466 | 0.0991 | 0.164 | 460 | 490 | 350 | 370 |
| 4×240 | 1.7 | 60.4 | 12672 | 60.4 | 6666 | 0.0754 | 0.125 | 530 | 580 | 410 | 440 |
| 4×300 | 1.8 | 65.7 | 15302 | 65.7 | 7795 | 0.0601 | 0.100 | 590 | 660 | 460 | 520 |
| 4×400 | 2.0 | 74.2 | 19969 | 74.2 | 10319 | 0.047 | 0.0778 | 670 | 750 | 523 | 615 |
| Note:* means round conductor | |||||||||||




For more about wires and cables, please feel free to CLICK IT.
Established in 1994,Henway Electric Group Inc has now developed into an innovative enterprise with strong R&D ability after 20 years in the industry. It covers an area of 210,000 square meters and has more than 2,000 employees. It has successively introduced about 2,000 items of advanced
1. Q:How does your factory control the quality?
A:Factory has a quick and enthusiastic merchandisers team, strict and responsible QC team, service for many well-known brands all around the world with our high-quality products and strict.